PGS-3-500-C
Silent Enclosure
400 Kw/ 500 KvaCummins Diesel

Cummin KTA19-G2

4.9 (14 Reviews)

500 KVA three phase diesel generator set with Cummins engine featuring DEEP SEA ELECTRONICS control module, automatic battery charger with two-stage charging, and nano-technology battery safety features. Includes sound proof/weather proof steel enclosure and comprehensive engine protection system.

Standby

400 Kw/ 500 Kva

Prime

360 Kw/ 450 Kva

Fuel

Diesel

Hz

60Hz

Unit Operational Rating

Altitude

1500m

Amb. Temp

40°C

Derating

1% per 100m above 1500m

Standby Limits & Overload

500 hours during one year (300 hours for continues use) | 10% Overload

Core System Configuration

Engine Model

Cummin KTA19-G2

Enclosure Type

Silent

Standby Power

400 Kw/ 500 Kva

Prime Power

360 Kw/ 450 Kva

Operating Speed

1800rpm

Speed Control

Electronically

Frequency

60Hz

Phase Mode

Three Phase

Starting Voltage

24v

Fuel Type

Diesel

Fuel Autonomy

Good for 8 Hours

Weight

2350 Kgs

Dimensions

L 440 x H 180 x W 240 cm

Voltage Options

208v/120v 220v/127v 240v/139v 380v/220v 440v/254v 480v/277v

Engine Infrastructure

CYLINDERS

6 inline

ASPIRATION

Turbocharged, Air-air after-cooled

CYCLE

4

COMBUSTION

Direct Injection

COOLING

Water Cooled

BORE STROKE

130 X 163

COMPRESSION

17:1

DISPLACEMENT

13 L

Alternator Architecture

TECHNOLOGY

Stamford Technology

INSULATION

Class H

EXCITATION

Self-Excitation or PMG

PROTECTION

Ip23